3-phase Grid measurement inputs | 2 x 3-phase(L1;L2;L3;N 400 VAC/690 VAC 1 x 3-phase (L1;L2;L3;N) 1A/5A Class 0.5 (Power) Class 0.2 (U; I) |
Altitude | Up to 4000 m; refer to module specification for over 2000 m |
Analogue Inputs | 0/24 VDC with wire break detection 0...10 V +/-10 V 0...20 mA 4...20 mA PT100 2-wire PT1000 2-wire Thermocouple(E;J;K;N;R;S;T) RMI (0..4.5 kOhm) |
Analogue Outputs | +/-10V +/-25 mA 1..10V PWM (0...2500Hz) |
Approvals | CE; UL/ULC;DNV;BV |
Communication Protocols | PCM3.1 EtherCAT master OPC DA OPC UA Server CANOpen Master CANOpen Slave Modbus TCP Slave Modbus TCP Master HTTPS/WSS/JSON (CVI) J1939 |
Concept | Base mount for increased stability |
Connector type | Connector w. screw |
Cooling | Passive |
Depth (incl. connectors) | 158 |
Digital Inputs | 24 VDC (+/-36V...+/-8V) Frequency Counter (Up to 20kHz) |
Digital Outputs | 24 VDC DO Relay Outputs |
EtherCAT ports | 2 (via PSM3.1) |
Ethernet | 5 switched (managed) 100 Mbps |
Ethernet ports | 5 switched 100 Mbit/s |
Expandable storage | SD card slot |
Fieldbusses | Ethernet EtherCAT with cable redundancy CAN |
Frequency | 35 to 78 Hz |
Hardware design life time | no less than 10 years @ 40 °C |
Height [mm] | 168 |
Internal Storage | 512 MB |
IO modules | Up to 6 per rack |
Memory (RAM) | 256 MB |
Operating System | DEIF In-house maintained Operating System (BSPv4) Real-time patched Linux® n-device web-based configuration Fail-safe system software start up with two OS images (active and fault-back) Power fail-safe; self-monitoring and error correcting file system Simplified update procedures (no special tools; same for OS and firmware) |
Operating System (Cont) | Secured Certificated based access by standard protocols User access management (Operator; Service and Administrator); rights and credentials Network configuration of the build-in 5 port switch (VLAN) IPv4 and IPv6 support Network Time protocol support as Client and Server Secured communication with certificated based authentication access by standard protocols Discover the device via hostname (mDNS services) Device backup and restore Secure boot (Chain-of-trust) |
Operating Temperature | -40 °C ... 70 °C |
Persistent storage | Via CmpApp to Internal flash |
PLC runtime | CODESYS V3 SP15 or later |
Processor | 400 MHz Power based CPU |
Programming | Available on request |
Protection Class | IP21 |
Real-time Clock(RTC) | |
Relative humidity | 97 % 55 °C condensation |
Start up temperature | -40 °C |
Storage | -40 °C ... 85 °C |
Typical applications | Trains Mobile Power generation Gen-set control Facility Building automation Marine Propulsion |
USB Host | 0 |
Vibrations (Bump) | 20 g; 16 ms; half sine (IEC 60255-21-2 class 2) |
Vibrations (Endurance) | 10 to 150 Hz: 2 g (IEC 60255-21-1 class 2) |
Vibrations (Operational) | 3 to 8 Hz: 17 mm peak-peak 8 to 100 Hz: 4 g 100 to 500 Hz: 2 g |
Vibrations (Response) | 10 to 58.1 Hz: 0.15 mm peak-peak 58.1 to 150 Hz: 1 g ( IEC 60255-21-1 class 2) |
Vibrations (Seismic) | 3 to 8.15 Hz: 15 mm peak-peak 8.15 to 35 Hz: 2 g (IEC 60255-21-3 class 2) |
Vibrations (Shock) | 10 g; 11 ms; half sine (IEC 60255-21-2 Response class 2) 30 g; 11 ms; half sine (IEC 60255-21-2 Endurance class 2) 50 g; 11 ms; half sine (IEC 60068-2-27) |
Width [mm] | See datasheet |